외기온도에 따른 프리쿨링 시스템의 성능 특성 및 경제성평가
- Alternative Title
- A study on Performance Characteristic and Energy Saving of Free Cooling System according to outdoor temperature
- Abstract
- With growing the industry, the case that requires the cooling load in winter is increasing. therefore, the demand for energy is rapidly increased in the winter as well as summer. To solve the this problem the free cooling system is develop. The free cooling system use the cooled outdoor temperature to cool the water. Usually it uses the cooling tower in order to cool the water. But the cooling tower has problems that are installation for cooling tower, freeze and burst. In order to solve the problem, the free cooling system with dry-cooler is suggested. In case of the foreign country the study for the free cooling system with dry-cooler is active but in case of the domesticity the study for it is deficient. Thus, in this study the free cooling system with dry-cooler is analyzed. Also, the national adaptability for the free cooling system is examined using economic analysis base on the outdoor temperature in the domesticity.
The free cooling system has the three cases which are explained in the body of the study. Through the experiment, the electric power, outlet water temperature and cooling load are measured with the tree cases. In the result of the experiment, the measuring efficiency is about 10 percent between experiment data and simulation data. Through the experiment, the credibility of simulation is checked. When the free cooling system is used for the data center and industrial process, the energy saving rate is approximately 38 percents. Using the previous result, the economic evaluation based on free cooling system is conducted. Through the evaluation, the free cooling system has a refund before a year. Thus, when the existing cooler have used for 10 years, the free cooling system is better than existing cooler.
- Author(s)
- 김희민
- Issued Date
- 2016
- Awarded Date
- 2016. 2
- Type
- Dissertation
- Publisher
- 부경대학교 대학원
- URI
- https://repository.pknu.ac.kr:8443/handle/2021.oak/13088
http://pknu.dcollection.net/jsp/common/DcLoOrgPer.jsp?sItemId=000002233622
- Alternative Author(s)
- Kim Hee Min
- Affiliation
- 부경대학교 대학원
- Department
- 대학원 냉동공조공학과
- Advisor
- 윤정인
- Table Of Contents
- 목 차
Abstract ⅲ
List of figures ⅴ
List of table ⅶ
Nomenclature ⅷ
제 1 장 서론
1.1 연구 배경 및 목적 1
1.2 종래연구 3
제 2 장 이론적 고찰
2.1 프리쿨링 시스템의 개요 4
2.2 열역학 모델식 6
제 3 장 프리쿨링 시스템의 성능분석
3.1 시뮬레이션 조건 7
3.2 프리쿨링 시스템의 성능분석
3.2.1 프리쿨링 시스템의 작동범위 10
3.2.2 외기온도에 따른 압축일량 12
3.2.3 요구냉수온도에 따른 성능분석 14
3.3 일정 조건에서의 실험
3.3.1 실험장치도 16
3.3.2 실험조건 및 방법 17
3.3.3 실험결과 19
3.4 실제 데이터와 시뮬레이션 데이터의 비교 23
제 4 장 프리쿨링 시스템의 경제성평가
4.1 경제성 평가 방법 및 조건 26
4.2 연간 에너지 사용량 분석 28
4.2.1 데이터센터 29
4.2.2 산업공정 31
4.3 경제성 평가 및 민감도 분석 33
4.3.1 데이터센터 34
4.3.2 산업공정 39
제 5 장 결론 44
참고문헌 46