PUKYONG

Bubble Jet Loop Heat Pipe의 증발부 형상에 따른 근권난방 시스템의 성능특성에 관한 연구

Metadata Downloads
Abstract
Korea's winter horticulture is done by hot air furnace, and more than 95% is used as a diesel fuel. In order to winter cultivation the soil temperature must be maintain above 16 ~ 18 ℃. Facility horticulture farmers have great difficulty due to sharp increase in international oil price. Thus, the study is needed for reduce oil consumption and improve the productivity of horticulture farmers.
In this study, Bubble Jet Loop Heat Pipe(BJLHP) was applied to the root heating system.
Bubble Jet Loop Heat Pipe generates the forced nucleate boiling by heater in evaporating section, and the boiling heat is transported to condensation section by bubble oscillation and circulation. So it is possible to overcome low efficiency in horizontal condition of heat pipe. I conducted two kinds of fundamental studies to improve the performance of BJLHP. First we changed clearance of annual space in evaporating section as 0.79mm, 2.17mm and 3.76mm. As a result of this study, case of clearance 2.17mm showed good thermal performance of three cases. And then we used enhanced boiling surfaces in evaporation section to improve the thermal performance. We used sinter tube, enhanced boiling tube and compared with smooth tube. Sinter tube BJLHP shows best thermal performance of three types.
In this study BJLHP was designed by length 4m, and heat source is cartridge type electric heater(220V-100W). Heater input capacity was changed by slidacs 25W, 50W, 75W and 100W. And then each case of BJLHP temperature was measured. And I tested on-off system according to controlled deviation using temperature controller.
As a result the temperature difference between evaporating section and condensing section is 1℃ in case of 100W. So the device showed a uniform temperature as a whole. And effective thermal conductivity is 2,721 kW/m·K. It means BJLHP thermal conductivity is 6800 times better compared with copper.
BJLHP was installed in strawberries farm located in gimhae. When BJLHP operating soil temperature was kept at about 18℃.
Author(s)
신종석
Issued Date
2014
Awarded Date
2014. 2
Type
Dissertation
Publisher
부경대학교
URI
https://repository.pknu.ac.kr:8443/handle/2021.oak/1331
http://pknu.dcollection.net/jsp/common/DcLoOrgPer.jsp?sItemId=000001966740
Affiliation
대학원
Department
대학원 냉동공조공학과
Advisor
김종수
Table Of Contents
제 1 장 서론 1
1.1 연구목적 및 배경 1
1.2 국내 시설원예용 난방 기술 수준 3
제 2 장 BJLHP의 개요 및 성능향상 연구 5
2.1 BJLHP의 작동원리 5
2.2 기초이론 및 성능향상 연구
2.2.1 증발부 간극(Clearance)에 따른 BJLHP 7
2.2.2 비등촉진 전열면 증발부에 따른 BJLHP 18
2.3 작동유체 선정 26
제 3장 실험장치 및 방법 32
3.1 실험장치 32
3.2 실험방법 38
제 4장 실험결과 41
4.1 히터 입열량에 따른 BJLHP 열적성능 41
4.2 BJLHP 작동에 따른 토양 온도분포 46
4.3 BJLHP 작동에 따른 전력소모량 50
제 5장 결론 51
참고문헌 53