상변화물질PCM을 이용한 소방배관의 동파방지에 관한 연구
- Abstract
- Freeze accidents are frequently occurring due to low outside temperatures in winter. In particular, if the fire piping is frozen, it is exposed to the risk of fire during the maintenance period. Various methods are used to solve this problem, but there is a risk of fire or installation costs are expensive. Therefore, in this study, PCM is used to prevent freezing or to reduce power consumption of heating wires.
First, a numerical analysis model was created by using a finite difference method in the Matlab program. After that, the numerical analysis model was verified by comparing it with the actual measurement experiment results. Through numerical analysis simulation, it was confirmed that when PCM was used, the freezing time was delayed and freeze was prevented compared to general insulation fire piping. In the case of fire piping with heating wires, it was confirmed that the use of PCM reduced the operation rate of heating wires, thereby reducing power consumption.
Finally, in this study, information on whether PCM selection and heating wire installation are necessary is required for proper design of fire piping. Therefore, a regression equation was proposed to predict the freezing time through linear regression analysis of freezing time data according to various regions, latent heat, melting point, and PCM volume.
- Author(s)
- 김영해
- Issued Date
- 2022
- Awarded Date
- 2022. 2
- Type
- Dissertation
- Keyword
- 상변화물질 동파 잠열 수치해석
- Publisher
- 부경대학교
- URI
- https://repository.pknu.ac.kr:8443/handle/2021.oak/24276
http://pknu.dcollection.net/common/orgView/200000602017
- Affiliation
- 부경대학교 대학원
- Department
- 대학원 냉동공조공학과
- Advisor
- 금종수
- Table Of Contents
- 제 1장 서 론 1
1.1 연구 배경 및 목적 1
1.2 기존 연구 3
1.3 연구 범위 4
제 2장 기초 이론 5
2.1 1차원 정상 상태 전도 열전달 5
2.2 1차원 과도 전도 열전달 7
2.3 대류 열전달 8
2.4 유한차분법(Finite Difference Method) 11
2.5 상변화물질(Phase Change Material : PCM) 12
2.6 상변화 판별법 13
제 3장 실측 실험 14
3.1 수치해석 14
3.2 실험 방법 14
3.3 실험 결과 18
제 4장 PCM의 동파방지 효과 20
4.1 실험 목적 20
4.2 실험 방법 20
4.3 실험 결과 22
제 5장 열선이 설치된 소방배관에서 PCM의 전력사용량 절감효과 23
5.1 실험 목적 23
5.2 실험 방법 23
5.3 실험 결과 25
제 6장 PCM인자별 동파방지 효과와 동결시간 예측 28
6.1 실험 목적 28
6.2 실험 방법 28
6.3 인자 선정 28
6.4 실험 결과 31
6.4.1 PCM의 인자별 동파방지 효과 31
6.4.2 지역에 따른 소방배관의 동결시간 33
6.5 선형회귀분석 36
6.5.1 변수 36
6.5.2 선형회귀분석 결과 37
제 7장 결 론 39
참고문헌 41
Appendix 44
감사의 글 62
- Degree
- Master
-
Appears in Collections:
- 대학원 > 냉동공조공학과