외부 감육 직관의 내압에 의한 파괴 기준
- Abstract
- The pipelines are subject to erosion/corrosion, because of the high-speed flow of water and steam with high temperatures/high pressures. This study carried out an experimental and finite element analysis on the fracture behavior of straight pipes with local wall thinning under internal pressure. Local wall thinning was machined on the pipes, in order to simulate erosion/corrosion metal loss. The configurations of the eroded area included an eroded ratio of d/t=0.80∼0.92, and an eroded length of l=25, 50 and 102 mm. Three-dimensional elastic-plastic analyses were also carried out using the finite element method, which is able to accurately simulate failure behaviors. In regards to the relationship between pressure and eroded ratio, the criteria that can be used safely under operating pressure and design pressure were obtained from this calculation. The results of this calculation were in relatively good agreement with that of the experiment.
- Author(s)
- 김수영
- Issued Date
- 2013
- Awarded Date
- 2013. 8
- Type
- Dissertation
- Publisher
- 부경대학교
- URI
- https://repository.pknu.ac.kr:8443/handle/2021.oak/25533
http://pknu.dcollection.net/jsp/common/DcLoOrgPer.jsp?sItemId=000001966607
- Affiliation
- 대학원
- Department
- 대학원 기계공학학ㆍ연협동과정
- Advisor
- 남기우
- Table Of Contents
- 목 차
Abstract
1. 서 론 1
2. 해석 방법 2
3. 재료 및 실험방법 4
3.1 재료 및 시험편 4
3.2 실험방법 6
4. 결과 및 고찰 11
4.1 유한요소법에 의한 해석 7
4.2 내압에 의한 파괴 실험 26
5. 결 론 34
참고문헌
감사의 글
- Degree
- Master
-
Appears in Collections:
- 대학원 > 기계공학학연협동과정
- Authorize & License
-
- Files in This Item:
-
Items in Repository are protected by copyright, with all rights reserved, unless otherwise indicated.