우수를 이용한 옥상층 열부하저감에 관한 실험 연구
- Alternative Title
- A Experimental Study on thermal load reduction of rooftop using rainwater
- Abstract
- The Flat roof type has thermal condition poorly. The two model were made to be improved thermal load reduction of flat roof type. The one is stored rainwater on the flat roof, the other is not stored rainwater on the flat roof.
(1)The surface temperature of the stored rainwater in the roof top is showed average 6.2℃ lower than the surface temperature of existing roof by evaporation and thermal resistance.
(2)The ceiling surface temperature of the stored rainwater in the roof top is showed 0.1℃ lower than the surface temperature of existing roof on the condition of exposed outdoor.
(3)As the surface temperature is affected by the conductive heat transfer through roof, the stored rainwater in the roof top is showed 1.9 w/㎡ compared to the existing roof.
(4)The reduction of heat load is achieved by evaporation of the stored rainwater in the top roof is related air temperature, humidity and air velocity.
- Author(s)
- 이병현
- Issued Date
- 2007
- Awarded Date
- 2007. 2
- Type
- Dissertation
- Keyword
- 우수 옥상층 열부하 Rainwater Rooftop Thermal load
- Publisher
- 부경대학교 산업대학원
- URI
- https://repository.pknu.ac.kr:8443/handle/2021.oak/3610
http://pknu.dcollection.net/jsp/common/DcLoOrgPer.jsp?sItemId=000001953520
- Alternative Author(s)
- Lee, Byung-Hyun
- Affiliation
- 부경대학교 산업대학원
- Department
- 산업대학원 건축공학과
- Advisor
- 임영빈
- Table Of Contents
- 1. 서론 = 1
1.1 연구의 배경 및 목적 = 1
1.2 연구의 범위 및 방법 = 3
2. 이론적 고찰 = 5
2.1 기존 옥상층의 열평형 = 5
2.2 우수를 저장한 옥상층에서의 열평형 = 6
2.3 부하해석을 위한 건물 에너지 성능요소 = 9
3. 모델실험의 개요 및 측정데이타 = 12
3.1 모델실험의 개요 = 12
3.2 측정방법 및 장비 = 16
4. 측정 결과 분석 = 19
4.1 온도 = 19
4.2 상대습도 및 기류속도 = 29
4.3 전도열량 = 29
4.4 증발손실열량 = 39
5. 결론 = 41
참고문헌 = 42
Abstract = 44
- Degree
- Master
-
Appears in Collections:
- 산업대학원 > 건축공학과
- Authorize & License
-
- Files in This Item:
-
Items in Repository are protected by copyright, with all rights reserved, unless otherwise indicated.