건물 기계실에서 발생하는 설비소음의 특성에 관한 연구

Metadata Downloads
Alternative Title
A Study on the Characteristics of Building Equipment Noise Generates at Building Machine Room
Abstract
Noise degree that happen in equipment device that is situated in building machine room has measured. Result that grasp noise source speciality and examine noise estimation standard are as following.
Noise degree was measured by C characteristic and A characteristic. All Pass of equipment appliance appeared by each 67.7~102.7dB(C), 62.0~103.0dB(C). All Pass of measured transmission loss result in central unit appeared by each 54.2~72.8dB (C), 41.3~71.7dB(C).
Noise degree of equipment appliance was evaluated by N value that propose in architectural institute of Japan. Emergency generator appeared most greatly by N-85, and electric transformer appeared as is smallest by N-60. In central unit transmission loss application result by N-40~N-70 appear. This exceeds architectural institute of Japan permission standard, can speak that countermeasure need.
Noise degree of equipment appliance was evaluated by NR value that propose in ISO. Emergency generator appeared most greatly by NR-95, and electric transformer appeared as is smallest by NR-60. In central unit transmission loss application result by most NR-40 appear, and this is satisfying do acceptable level of large scale office.
Noise degree evaluated by appliance NC curve. Refrigerating machine, Water supply pump, Emergency generator, Cooling tower appeared most greatly by NC-70. Air conditioner and electric transformer appeared as is smallest by NC-60. Can speak that countermeasure need transmission loss department in reply because exceed acceptable level of office by an application a result NC-30~NC-60 in center watch department.
Above result can know that noise degree of equipment appliance is decided in most 1kHz frequency band. This is being expose by other result according to estimation method as well as exceed valuation basis of room noise. Therefore, noise of equipment appliance need to evaluate after choose suitable valuation basis. Specially, noise of equipment appliance that happen in machine room is judged that reduction countermeasure in 1kHz that is central frequency need.
Author(s)
정두환
Issued Date
2008
Awarded Date
2008. 2
Type
Dissertation
Keyword
설비소음 음압레벨 투과손실
Publisher
부경대학교 산업대학원
URI
https://repository.pknu.ac.kr:8443/handle/2021.oak/4049
http://pknu.dcollection.net/jsp/common/DcLoOrgPer.jsp?sItemId=000001984195
Alternative Author(s)
Jung, Doo-Hwan
Affiliation
부경대학교 산업대학원
Department
산업대학원 건축공학과
Advisor
임영빈
Table Of Contents
1. 서론 = 1
1.1 연구의 배경 및 목적 = 1
1.2 연구의 방법 및 범위 = 2
2. 이론적 고찰 = 3
2.1 실내소음의 평가기준 = 3
2.1.1 ㏈(A)(A보정 음압레벨) = 3
2.1.2 N곡선 = 4
2.1.3 NC곡선(Noise Criteria Curves) = 6
2.1.4 NR(Noise Rating)곡선 = 9
2.2 벽체의 투과손실 = 11
2.2.1 차음성능의 표시방법 = 11
2.2.2 구조체의 투과손실 = 13
2.3 기존 문헌 = 14
3. 설비소음의 측정 = 15
3.1 측정의 개요 = 15
3.1.1 대상실의 개요 = 15
3.1.2 측정항목과 측정장비 = 16
3.1.3 설비소음의 측정 = 17
3.1.4 측정 설비기기의 개요 = 20
3.2 측정지점 = 26
3.2.1 기계실내의 설비기기 배치 = 26
3.2.2 중앙감시실 벽체 단면상세 = 27
4. 측정결과 분석 및 고찰 = 28
4.1 주파수별 특성과 음압레벨의 변화 = 28
4.1.1 C특성에 의한 음압레벨 = 28
4.1.2 A특성에 의한 음압레벨 = 32
4.2 N곡선에 의한 평가 = 36
4.2.1 설비기기에 의한 N = 36
4.2.2 투과손실에 의한 N = 37
4.2.3 투과손실 적용 전·후의 N = 39
4.3 NC곡선에 의한 평가 = 41
4.3.1 설비기기에 의한 NC = 41
4.3.2 투과손실에 의한 NC = 42
4.3.3 투과손실 적용 전·후의 NC = 44
4.4 NR곡선에 의한 평가 = 45
4.4.1 설비기기에 의한 NR = 45
4.4.2 투과손실에 의한 분석 = 46
4.4.3 투과손실 적용 전·후의 NR = 49
5. 결론 = 50
참고문헌 = 52
Abstract = 53
감사의 글 = 55
Degree
Master
Appears in Collections:
산업대학원 > 건축공학과
Authorize & License
  • Authorize공개
Files in This Item:

Items in Repository are protected by copyright, with all rights reserved, unless otherwise indicated.